1. GENERALITIES
1.1 Description
The application is dedicated to the control and regulation of the Air Handling Units with cross flow recovery heat
exchanger. There are two solutions available:
COMPACT Control: Responds to minimum requirements and the Standards.
COMPLETE Control: Integrates the heating and high recovery efficiency functions to the Base solution.
The solution makes use of the large modularity of the c-pro 3 micro SAVE/c-pro 3 kilo SAVE
The c-pro 3 micro SAVE/c-pro 3 kilo SAVE controller has the following I/O:
Digital outputs: 9
Digital inputs: 9
Analogical inputs: 9
Analogical outputs: 6
Both instruments are equipped with CAN field port and a second RS485 serial interface (Modbus) allows connection to
BMS or EVCO (RICS) supervision systems.
The main control functions managed by the “Complete” solution are:
- Supply fan management
- Return fan management
- Management of the cross flow recovery heat exchanger by-pass damper
- Outside air damper management
- Management damper mixing room
- Management of hot water coil for heating (or a group of 3 electric heaters)
- Management of time bands with ECONOMY and COMFORT working mode
- CO
2
probe management for fan control
- Alarms log
- User Menu split in three main levels (User, Installer, Manufacturer), each protected by a different password.
- Multilanguage user menu (English, Italian, French)