PH04 Maximum CO
2
probe PPM value 1100 PH03 10000 ppm IS-V
PH05
Enables unit switch-on/off from
“Start/Stop” digital input
Yes (1) No (0) Yes (1) - IS-V
PH06 Enables unit switch-on/off from supervisor No (0) No (0) Yes (1) - IS-V
PH07 Minimum value Pa pressure probe 0 0 32000 Pa IS-V
PH08 Maximum value Pa pressure probe 3000 0 32000 Pa IS-V
PH18 Clear hystorical alarms NO (0) NO (0) YES (1) - IS-V
Set YES (1)
ad wait for
the NO (0)
PH20 Enable buzzer Yes (1) No (0) Yes (1) - IS-V
PH30
Temperature unit of measurement
0: °Celsius
1: °Fahrenheit
0 (°C) 0 (°C) 1 (°F) - IS-V
PH32
Language of user interface
(English, Italian, French)
ENG ENG FRE - IS-V
PH99 Reset the factory parameters default NO (0) NO (0) YES (1) - IS-D
Wait for the
NO (0)
value to be
read again
on reset
completion
PSd2 Installer level password (2) 0 -999 9999 - IS
Level 3 MANUFACTURER MENU
CONFIGURATION PARAMETERS
After modification of these parameters it is recommended to remove and then re-apply the power supply to the board.
PG00
Unit type:
1=Compact
2=Complete
2 1 2 - CO-G
PG01 Enabling bypass recuperation Yes (1) No (0) Yes (1) - CO-G
PG02
Selection of type of device for heating:
0: Disabled
1: Hot water coil only
2: Electric heater DO coil only
3: Electric heater AO coil only
3 0 3 - CO-G
PG03
Type of recovery heat exchanger by-pass
damper control:
0: Digital Control (DO7)
1: Analogue Control (AO3)
DO (0) DO (0) AO (1) - CO-G
PG04 Outside air damper enabling Yes (1) No (0) Yes (1) - CO-G
PG05 Enabling of post-ventilation Yes (1) No (0) Yes (1) - CO-G
PG06
Enabling of recovery heat exchanger anti-
freeze protection
Type 1
(1)
Disabled
(0)
Type 2 (2) - CO-G
PG08
Enabling of recovery heat exchanger by-pass
in summer
Yes (1) No (0) Yes (1) CO-G
PG09 Activation of outside air damper end run Yes (1) No (0) Yes (1) CO-G
PG10 Type of fan DO (0) DO (0) AO (1) - CO-G
If PF00=1
PG10=1