EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104
EVCO
page 10 of 68
AI 7 Not used
AI 8 Not used
AI 9 Not used
Serial ports
RS485 RS485 Modbus RTU
CAN bus To Vgraph
Digital inputs
DI 1 Presence sensor
DI 2 Start – Stop (remote)
DI 3 Supply fan thermal protection
DI 4 Return fan thermal protection
DI 5 Not used
DI 6 Not used
DI 7 Not used
DI 8 Not used
DI 9 Not used
Analogue outputs
AO 1 Not used
AO 2 Not used
AO 3 Recovery heat exchanger BY-PASS damper control (0-10 V) *
AO 4 Not used
AO 5 Not used
AO 6 Mixing room damper control (0-10 V)
Digital Outputs (Relay)
DO 1 Return fan first speed
DO 2 Return fan second speed
DO 3 Return fan third speed
DO 4 Supply fan first speed
DO 5 Supply fan second speed
DO 6 Supply fan third speed
DO 7 Recovery heat exchanger BY-PASS damper control *
DO 8 Not used
DO 9 Not used
(*) The recovery heat exchanger BY-PASS damper control can be analogic or digital, and
setting with clock
RTC system clock - Real Time Clock.
For driving the 3-speed fans (Digital output) set PG10=DO