EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104
EVCO
page 40 of 68
PA24 RTC alarm enabling Active (1)
Not-
active
(0)
Active
(1)
- CO-S
PA26 Probes alarms signals delay 10 0 240 Sec CO-S
PA51
Type of alarm fire/smoke
0: Not-active
1: Off by allarm
2: Forcing 1
3: Forcing 2
1 0 3 - CO-S
VARIOUS PARAMETERS
PH11 Board Modbus address 1 1 247 - CO-V
PH12
Communication Baud Rate for the board
(0=1200, 1=2400, 2=4800, 3=9600,
4=19200)
3 0 4 - CO-V
PH13 ModBus Parity (0=none, 1=Odd, 2=Even) 2 0 2 - CO-V
PH14 Stop Bit ModBus (0=1bit, 1=2bit) 0 0 1 - CO-V
PH40 Enable outlet temperature probe Yes (1) No (0) Yes (1) - CO-V
PH41 Enable return temperature probe Yes (1) No (0) Yes (1) - CO-V
PH42 Enable CO
2
probe No (0) No (0) Yes (1) - CO-V
PH43 Enable outside air temperature probe Yes (1) No (0) Yes (1) - CO-V
PH44
Enable pressure probes
0: Not-active
1: probe 1
2: probe 2
0 0 2 - CO-V
PH45
CO
2
sensor probe
0: 0-20mA
1: 4-20mA
2: 0-5V
3: 0-10V
0-10V (3)
0-20mA
(0)
0-10V
(3)
- CO-V
PH46
Pressure sensor probes
0: 0-20mA
1: 4-20mA
2: 0-5V
3: 0-10V
0-10V (3)
0-20mA
(0)
0-10V
(3)
- CO-V
PH47
Analog output-type electric heaters
0: 0-10V
1: PWM
0-10V (0)
0-10mA
(0)
PWM (1) - CO-V
PH51 Logic of the digital input DI1 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH52 Logic of the digital input DI2 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH53 Logic of the digital input DI3 N.C. (1) N.O. (0) N.C. (1) - CO-V
PH54 Logic of the digital input DI4 N.C. (1) N.O. (0) N.C. (1) - CO-V
PH56 Logic of the digital input DI5 N.C. (1) N.O. (0) N.C. (1) - CO-V
PH57 Logic of the digital input DI6 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH58 Logic of the digital input DI7 N.C. (1) N.O. (0) N.C. (1) - CO-V
PH59 Logic of the digital input DI8 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH60 Logic of the alarm relay DI9 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH61 Logic of the alarm relay DO12 N.O. (0) N.O. (0) N.C. (1) - CO-V