EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104
EVCO
page 31 of 68
PH99 Reset the factory parameters default NO (0) NO (0) YES (1) - IS-D
Wait for the
NO (0)
value to be
read again
on reset
completion
PSd2 Installer level password (2) 0 -999 9999 - IS
Level 3 MANUFACTURER MENU
CONFIGURATION PARAMETERS
After modification of these parameters it is recommended to remove and then re-apply the power supply to the board.
PG00
Unit type:
1=Compact
2=Complete
1 1 2 - CO-G
PG01 Enabling bypass recuperator Yes (1) No (0) Yes (1) - CO-G
PG02
Selection of type of device
for heating:
0: Disabled
1: Hot water coil only
2: Electric heater coil only DO
3: Electric heater coil only AO
Disabled
(0)
Disabled
(0)
Heaters
(3)
- CO-G
PG03
Type of recovery heat exchanger by-pass
damper control:
0: Digital Control (DO7)
1: Analogue Control (AO3)
AO (1) DO (0) AO (1) - CO-G
PG04 Outside air damper enabling No (0) No (0) Yes (1) - CO-G
PG05 Enabling of post-ventilation No (0) No (0) Yes (1) - CO-G
PG06
Enabling of recovery heat exchanger anti-
freeze protection
Type 1
(1)
Not-active
(0)
Type 2 (2) - CO-G
PG08
Enabling of recovery heat exchanger
by-pass in summer
No (0) No (0) Yes (1) CO-G
PG09 Activation of outside air damper limit switch No (0) No (0) Yes (1) CO-G
PG10 Type of fan DO (0) DO (0) AO (1) - CO-G
If PF=1
PG10=1
PG11 Enabling of mixing room damper No (0) No (0) Yes (1) - CO-G
PSd1 User level password (1) 0 -999 9999 - CO-G
PSd2 Installer level password (2) 0 -999 9999 - CO-G
PSd3 Manufacturer level password (3) 0 -999 9999 - CO-G
FANS
PF06
Minimum time that must pass for the switch-
on/off of each individual step of the fans
3 0 999 Sec CO-F
PF07
Temperature setpoint of the fans for anti-
freeze protection of the recovery heat
exchanger
2.0 PH01 PH02
°C
°F
CO-F
PF08
Differential for anti-freeze protection of
the recovery heat exchanger
2.0
0.0
0.0
20.0
36.0
°C
°F
CO-F
PF09
Minimum stand-by time before requesting
switch-off of a further fan step
5 1 99 Min CO-F