EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104
EVCO
page 34 of 68
3: 0-10V
PH51 Logic of the digital input DI1 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH52 Logic of the digital input DI2 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH53 Logic of the digital input DI3 N.C. (1) N.O. (0) N.C. (1) - CO-V
PH54 Logic of the digital input DI4 N.C. (1) N.O. (0) N.C. (1) - CO-V
PH56 Logic of the digital input DI5 N.C. (1) N.O. (0) N.C. (1) - CO-V
PH57 Logic of the digital input DI6 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH58 Logic of the digital input DI7 N.C. (1) N.O. (0) N.C. (1) - CO-V
PH59 Logic of the digital input DI8 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH60 Logic of the alarm relay DI9 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH61 Logic of the alarm relay DO12 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH80
CAN communication Baud Rate
(20K, 50K, 125K, 500K)
1 1 4 - CO-V
Note: Once the unit parameters have been configured and at each modification of the configuration parameters it is
recommended to switch OFF / switch ON the power supply to the board to make sure the configuration has been
correctly updated.
5.2 COMPLETE solution list of configuration parameters
Code Parameter description Default Min Max UM Menu Notes
Level 1 USER MENU
USER
SPHM Supply temperature heating setpoint 22.0 PH01 PH02
°C
°F
UT
SPHR Return temperature heating setpoint 20.0 PH01 PH02
°C
°F
UT
PF02
Speed/Capacity fans in manual regulation
mode
V3 V0 V3 UT
Only if
PF01=0
(Manual
Regulation)
PSd1 User level password (1) 0 -999 9999 - UT
Level 2 INSTALLER MENU
CLOCK
PT01 Start of the COMFORT time period 8:00:00 00:00:00 23:59:59 - OR
PT02 Start of the ECONOMY time period 20:00:00 00:00:00 23:59:59 - OR
PT11 Sunday
0
Working
0
Working
1
Not Working
OR
PT12 Monday
0
Working
0
Working
1
Not Working
OR
PT13 Tuesday
0
Working
0
Working
1
Not Working
OR
PT14 Wednesday
0
Working
0
Working
1
Not Working
OR
PT15 Thursday
0
Working
0
Working
1
Not Working
OR
PT16 Friday 0 0 1 OR