Working Working Not Working
PT17 Saturday
0
Working
0
Working
1
Not Working
OR
MAINTENANCE
PM01
Functioning hours maximum limit for fans.
The relevant alarm will be triggered over
this limit
8000 0 100000 Hours IS-MA
PM02 Outlet fan functioning hours 0 0 100000 Hours IS-MA
PM03 Return fan functioning hours 0 0 100000 Hours IS-MA
PM90
Last date on which maintenance was
performed on the machine
IS-MA
PM11
Calibration of the anti-freeze air
temperature probe
0.0
-10.0
-18.0
10.0
18.0
°C
°F
IS-MA
PM12
Calibration of the outlet air temperature
probe
0.0
-10.0
-18.0
10.0
18.0
°C
°F
IS-MA
PM13
Calibration of the return air temperature
probe
0.0
-10.0
-18.0
10.0
18.0
°C
°F
IS-MA
PM14 Calibration of the CO
2
probe 0.0 -200 200 ppm IS-MA
PM15
Calibration of the outside air introduction
temperature probe
0.0
-10.0
-18.0
10.0
18.0
°C
°F
IS-MA
PM16 Calibration of the pressure probe 1 0.0 -200 200 ppm IS-MA
PM17 Calibration of the pressure probe 2 0.0 -2000 2000 Pa IS-MA
FANS
PF00
Type of fans control:
0: Speed
1: Capacity
0 0 1 - IS-F
PF01
Type of fans regulation:
0: Manual
1: Automatic
2: Automatic with presence sensor
3: Automatic with CO
2
sensor
0 0 3 - IS-F
PF03 Fans Speed/Capacity in COMFORT period V2 V1 V3 - IS-F
PF04 Fans Speed/Capacity in ECONOMY period V1 V0 V2 - IS-F
PF05 Fans Speed/Capacity in RTC error V0 V0 V3 - IS-F
Only if
PF01=1/2/3
PF12
Fans Speed/Capacity in COMFORT with
presence sensor active
V3 V1 V3 - IS-F
PF13
Speed/Capacity in case of « non working »
day
V0 V0 V3 - IS-F
PF14 Set point CO
2
probe 500 PH03 PH04 ppm IS-F
PF15 Proportional band CO
2
probe 600 0 1000 ppm IS-F
PF16 Type of CO
2
regulation 0 0 1 IS-F
If PF00=1
PF16=1
PF17 Integral time CO
2
regulation 0 0 300 sec IS-F
PF21 Speed variator value corresponding to speed V1 33.50 0.00 100.00 % IS-F
Vista de pagina 34