EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104
EVCO
page 36 of 68
PF22 Speed variator value corresponding to speed V2 66.50 0.00 100.00 % IS-F
PF23 Speed variator value corresponding to speed V3 100.00 0.00 100.00 % IS-F
PF30 Minimum speed for modulating fan 0.0 0.0 PF31 % IS-F
PF31 Maximum speed for modulating fan 100.0 PF30 100.0 % IS-F
PF32 Static pressure setpoint ramp adjustment 300 0 30000 Pa/min IS-F
PF33 V1 static pressure setpoint adjustment 300 0 30000 Pa IS-F
PF34 V2 static pressure setpoint adjustment 400 0 30000 Pa IS-F
PF35 V3 static pressure setpoint adjustment 500 0 30000 Pa IS-F
PF36 Setpoint adjustment proportional band 200 0 10000 Pa IS-F
PF37 Integral time setting static pressure 0 0 300 Sec IS-F
PF38
Speed controller for pressure switch in
probe error
30.0 0.0 100.0 % IS-F
HEATING COILS
This menu is only accessible if PG02>0
Pb01
Regulation probe for heating
0: Supply Probe
1: Return Probe
0 0 1 IS-B
FREECOOLING
Pr04
Outside air/recovery heat exchanger by-
pass temperature set point in summer
15.0 PH01 PH02
°C
°F
IS-FC
Pr05
Return air/recovery heat exchanger by-
pass temperature set point in summer
22.0 PH01 PH02
°C
°F
IS-FC
ALARM PARAMETERS
PA01 Enabling fans working hours alarm Active (1)
Not-
active
(0)
Active (1) - IS-S
PA02
Signals working hours alarms on alarm
relay
No (0) No (0) Yes (1) - IS-S
PA04
Signals the supply/return fans thermal
overload alarm on the alarm relay
Yes (1) No (0) Yes (1) - IS-S
PA07
Differential pressure switch alarm delay on
unit start-up
60 0 999 sec IS-S
PA11
Signals the coil anti-freeze alarm on the
alarm relay
Yes (1) No (0) Yes (1) - IS-S
Only if
PG02=1
PA15
Signalling of the outside air damper limit
switch alarm on alarm relay
Yes (1) No (0) Yes (1) - IS-S
PA21
Signalling of high/low temperature alarms
on the alarm relay
yes (1) No (0) Yes (1) - IS-S
PA23 Signalling fire/smoke on alarm relay Yes (1) No (0) Yes (1) - IS-S
PA25 Signals RTC alarm on alarm relay Yes (1) No (0) Yes (1) - IS-S
PA27 Signals probe alarms on alarm relay Yes (1) No (0) Yes (1) - IS-S
VARIOUS PARAMETERS
PH01 Minimum temperature value -15.0
-20.0
-4.0
PH02
°C
°F
IS-V
PH02 Maximum temperature value 95.0 PH01
110.0
230.0
°C
°F
IS-V
PH03 Minimum CO
2
probe PPM value 0 0 PH04 ppm IS-V