PT14 Wednesday
0
Working
0
Working
1
Not Working
OR
PT15 Thursday
0
Working
0
Working
1
Not Working
OR
PT16 Friday
0
Working
0
Working
1
Not Working
OR
PT17 Saturday
0
Working
0
Working
1
Not Working
OR
Code Parameter description Default Min Max UM Menu Notes
MAINTENANCE
PM01
Max number of fans working hours.
The relevant alarm occurs over this limit
8000 0 100000 Hours IS-MA
PM02
Supply fan
working hours
0 0 100000 Hours IS-MA
PM03
Return fan
working hours
0 0 100000 Hours IS-MA
PM90
Last maintenance
date
IS-MA
PM11
Anti-freeze air temperature
probe offset
0.0
-10.0
-18.0
10.0
18.0
°C
°F
IS-MA
FANS
PF00
Type of fans control:
0: Speed
1: Capacity
0 0 1 IS-F
PF01
Type of fans regulation:
0: Manual
1: Automatic
2: Automatic with presence sensor
3: Automatic with CO
2
probe
0 0 3 IS-F
PF03
Speed/Capacity fans in
COMFORT period
V2 V1 V3 IS-F
PF04
Speed/Capacity fans in
ECONOMY period
V1 V0 V2 IS-F
PF05 Speed/Capacity fans in RTC error V0 V0 V3 IS-F
Only if
PF01=1/2/3
PF12
Speed/Capacity fans in COMFORT with
presence sensor active
V3 V1 V3 IS-F
PF13
Speed/Capacity in case of
« non Working » day
V0 V0 V3 IS-F
PF21
Speed variator value corresponding
to speed V1
33.50 0.00 100.00 % IS-F
PF22
Speed variator value corresponding
to speed V2
66.50 0.00 100.00 % IS-F
PF23
Speed variator value corresponding
to speed V3
100.00 0.00 100.00 % IS-F