C-PRO KILO AHU APPLICATION MANUAL
Pag. 81
7.2 Table of Alarms
The following is a list of all the alarms managed by the application. The order of
presentation is the same as the order of presentation for the active alarms. All alarms can be
viewed even when the mahcine is off.
Code Description of alarm Re-arm
Consequence Delay
AL01 Thermal delivery fan (*²) Auto
Shuts down all devices Fixed 2 sec.
AL02 Thermal pickup fan (*²) Auto
Shuts down all devices
Fixed 2 sec.
AL03 Alarm inverter delivery fan (*²) Auto
Shuts down all devices
Fixed 2 sec.
AL04 Alarm inverter pickup fan (*²) Auto
Shuts down all devices
Fixed 2 sec.
AL05 Thermal circulation pump Auto
Stops the pump Fixed 2 sec.
AL08 Air filter pressure switch A/M
Visualization May be set
AL09 Humidifier A/M
Stops the humidifier May be set
AL10 Airflow meter (*²) Manu
Shuts down all devices May be set
AL11 Anti-freeze Auto
Shuts down fans and closes the
shutter
Forces heating coil to 100%
Forces cooling coil to 0%
May be set
AL13 Fire/smoke Alarm (*²) Auto Shuts down all devices
-
AL14 Operating hours – delivery fans Manu*¹ Visualization -
AL15 Hours of operation – Uptake fan Manu*¹ Visualization -
AL16 Hours of operation – Heating pump Manu*¹ Visualization -
AL17 Hours of operation – Cooling pump Manu*¹ Visualization -
AL18 Ambient air probe broken or disconnected Auto
Inhibits the regulations upon
which the probe is dependent
May be set
AL19 Air delivery probe broken or disconnected Auto
Inhibits the regulations upon
which the probe is dependent
May be set
AL20 External air probe broken or disconnected Auto
Inhibits the regulations upon
which the probe is dependent
May be set
AL21
Ambient humidity probe broken or
disconnected
Auto
Inhibits the regulations upon
which the probe is dependent
May be set
AL22
Air delivery pressure probe broken or
disconnected
Auto
Inhibits the regulations upon
which the probe is dependent
May be set
AL23
Anti-freeze temperature probe damaged or
disconnected
Auto
Inhibits the regulations upon
which the probe is dependent
May be set
AL25
Pre-heating air temperature probe damaged
or disconnected
Auto
Inhibits the regulations upon
which the probe is dependent
May be set
AL26
VOC probe (or CO2) damaged or
disconnected
Auto
Inhibits the regulations upon
which the probe is dependent
May be set
AL27
External air humidity probe damaged or
disconnected
Auto
Inhibits the regulations upon
which the probe is dependent
May be set
AL28 RTC Alarm broken or discharged A/M
Inibits management of the time
zone
-
AL29 Expansion alarm Auto Stops devices on expansion May be set
A/M: Automatic or Manual alarm (set from parameter)
(*¹) To re-arm alarms connected to the hours of operation you need only reset the hours on the device
to zero.
(*²) These alarms cause the unit to shutdown bringing it to the status OFF from alarm
Note. To activiate the alarms derived from the digital contacts you need to set to a value
greater than zero the relative position for which the dedicated digital inputs will be
connected. If the position is zero the alarm is not managed. A position may be repeated only
once; it is not possible to manage the same position like “OR” for additional alarms.