C-PRO KILO AHU APPLICATION MANUAL
Pag. 33
not present
Pb03 Neutral zone for the regulation of temperature 4.0 0.0 20.0 °C IS-B
Pb05
Maximum shifting for Set Point calculation
running of delivery
0.0 0.0 20.0 °C IS-B
If Pb05=0
function not
enabled
Pb06
Proportional band for the Set Point calculation
running of delivery
5.0 0.0 20.0 °C IS-B
Pb10 Opening of heating valves alarm probe delivery 30.0 0.0 100.0 % IS-B
Pb11 Opening of cooling valves alarm probe delivery 30.0 0.0 100.0 % IS-B
Pb20
Insertion/release time single stage of resistance
for the post-heating
60 0 999 Sec IS-B
HUMIDITY
Menu accessible only if PG06>0 or PG12=1
PU02 Neutral zone for the regulation of humidity 6 0 100 % IS-U
PU03 Differential for the regulation of humidity 10 0 100 % IS-U
PU04
Integral time for the regulation of
dehumidification (with cold coil)
0 0 999 Sec IS-U
If PU04=0
ntegral action
not present
PU05 Enable functional limit for the dehumidification NO (0) NO (0) YES (1) - IS-U
PU10
Enable humidifier control with delivery
temperature
YES (1) NO (0) YES (1) - IS-U
PU11
Set Point on the delivery temperature to enable
the humidifier
22.0 PH03 PH04 °C IS-U
Only if
PU10=1
PU12
Differential on the delivery temperature to
enable the humidifier
3.0 0.0 20.0 °C IS-U
Only if
PU10=1
VALVES
PV01
Proportional band for regulation of valves
(cooling/heating)
10.0 0.0 30.0 °C IS-Va
PV02
Integral time for regulation of valves
(cooling/heating)
0 0 999 Sec IS-Va
If PV02=0
integral action
not present
PV05
Maximum shifting for Set Point calculation
running of delivery
0.0 0.0 10.0 °C IS-Va
If PV05=0
function not
enabled
PV06
Proportional band for the Set Point calculation
running of delivery
5.0 0.0 20.0 °C IS-Va
PV10
Opening cooling/heating valves alarm probe
delivery
30.0 0.0 100.0 % IS-Va
EXTERNAL AIR SHUTTERS
Menu accessible only if PG07>0
PS01
Type of Free-Cooling / Free-Heating
0: Disabled
1: Free-Cooling / Free-Heating in temperature
2: Free-Cooling / Free-Heating heat exchanger
1 0 2 - IS-SE
PS02 Enable air quality control NO (0) NO (0) YES (1) - IS-SE
PS03
Shutter command type
0: Only for Free-Cooling/Free-Heating
1: Only for controlling air quality
2: Priority to the greater of the two requests
3: Average of the two requests
0 0 3 - IS-SE
PS04
Proportional band for the modulation of the
external air shutters
8.0 0.0 30.0 °C IS-SE
PS05 Minimum opening for the external air shutters 0.0 0.0 PS06 % IS-SE
PS06 Maximum opening for the external air shutters 100.0 PS05 100.0 % IS-SE
PS07
Run time for the external air shutters from 0% to
100%
120 0 3600 Sec IS-SE
PS08
Maximum time to maintain signal until end run
time on relay for external air shutters. Signal
will shut off once maximum time is reached
5 0 600 Sec IS-SE