C-PRO KILO AHU APPLICATION MANUAL
Pag. 44
6.2.2 Unit in SUMMER operating mode (PG00=2)
The MOdE parameter can be setup by default in ESTATE (SUMMER).
Unit at single coil PG01=1.
The fan regulations can be set up by default in On/Off (PF01=1).
The primary regulation can be set up by default on the valve (PG04=1).
The regulation of the shutter is fixed (PG07=2).
PIN ANALOGUE INPUTS
AI1 Ambient air temperature probes (NTC)
AI2 Air delivery temperature probes (NTC)
AI3 Not utilized
AI4 Not utilized
AI5 Not utilized
PIN DIGITAL INPUTS
DI1 On/Off remote
DI2 Not utilized
DI3 Thermal delivery fan
DI4 Air filter pressure switch
DI5 Anti-freeze alarms
DI6 Air flow status
DI7 Not utilized
PIN ANALOGUE OUTPUTS
AO 1 Not utilized
AO 2 Cooling valve control (0-10V)
AO 3 Not utilized
PIN DIGITAL OUTPUTS
DO1 Delivery fan
DO2 Pickup fan
DO3 Not utilized
DO4 Opening external air shutters
DO5 Closing external air shutters
DO6 Dirty filter indicator
DO7 Alarm
RTC system clock present.