C-PRO KILO AHU APPLICATION MANUAL
Pag. 16
JD: Connection for the cut-phase output EVDFAN1 (analogue output 1; not utilized)
Conn. Label Description
JD-1 VDC Supplying power to cut-phase module EVDFAN1
JD-2 AO1 Cut-phase output module EVDFAN1
In order to utilize the cut-phase module EVDFAN1, it is necessary to supply power to the
controller in an alternate current; the current that powers the controller must be the same
current as that which is used to power the module.
JE: Connections for analogue outputs 2 and 3 (opto-isolator)
Conn. Label Description (Version V+V)
JE-1 AO2 0-10VDC
JE-2 GND Common analogue outputs
JE-3 AO3 0-10VDC
JF: Connections for controller power supply
Conn. Label Description
JF-1
V
Controller power supply (24VAC / 20 … 60 VDC)
JF-2
V
Controller power supply (24VAC / 20 … 60 VDC)
JG: Connections for network expansion I/O (not utilized) and for the remote keyboard (not
utilized)
Conn. Label Description
JG-1 VDC Remote keyboard power supply (12VDC, max. 50 mA)
JG-2 GND Common
JG-3 DATA Serial in tension
JM-JL-JI-JH: Connection for digital outputs
Conn. Label Description
JM-4 NO1 Contact normally open - output n.1
JM-3 CO1 Common output n.1
JM-2 NO2 Contact normally open - output n.2
JM-1 CO2 Common output n.2
JL-4 NO3 Contact normally open - output n.3
JL-3 CO3 Common output n.3
JL-2 NO4 Contact normally open - output n.4
JL-1 CO4 Common output n.4
JI-4 NO5 Contact normally open - output n.5
JI-3 CO5 Common output n.5
JI-2 NO6 Contact normally open - output n.6
JI-1 CO6 Common output n.6
JH-3 NO7 Contact normally open - output n.7
JH-2 NC7 Contact normally closed - output n.7
JH-1 CO7 Common output n.7
Vista de pagina 15