C-PRO KILO AHU APPLICATION MANUAL
Pag. 35
PA01 Enable alarms during hours of fan operation YES (1) NO (0) YES (1) - IS-S
PA02 Enable alarms during hours of pump operation NO (0) NO (0) YES (1) - IS-S
PA03
Signal alarms during hours of operation on
alarm relay
YES (1) NO (0) YES (1) - IS-S
PA04 Probe alarm delay 10 0 240 Sec IS-S
PA05 Signal alarm probe on alarm relay YES (1) NO (0) YES (1) - IS-S
PA06 Expansion alarm delay 5 0 999 Sec IS-S
PA08 Signal delivery fan alarm on alarm relay YES (1) NO (0) YES (1) - IS-S
PA09 Signal pickup fan alarm on alarm relay YES (1) NO (0) YES (1) - IS-S
PA10 Alarm delay thermal fans 2 0 999 Sec IS-S
PA11 Alarm delay inverter fans 2 0 999 Sec IS-S
PA15 Alarm delay thermal pumps 2 0 999 Sec IS-S
PA16 Signal alarms thermal pumps on alarm relay YES (1) NO (0) YES (1) - IS-S
PA20
Type of pressure switch alarm re-arm (dirty
recuperator)
0: Auto - Automatic
1: Manu - Manual
Manu (1) Auto (0) Manu (1) - IS-S
PA21 Pressure switch alarm delay (dirty recuperator) 30 0 999 Sec IS-S
PA24
Type of alarm re-arm pressure switch air filter
0: Auto - Automatic
1: Manu - Manual
Manu (1) Auto (0) Manu (1) - IS-S
PA25 Pressure switch air filter alarm delay 30 0 999 Sec IS-S
PA26
Signal alarms pressure switch air filter alarm
relay
YES (1) NO (0) YES (1) - IS-S
PA28 Reset airflow meter alarm delay 30 0 999 Sec IS-S
PA29 Airflow meter alarm delay 5 0 999 Sec IS-S
PA30 Signal alarm air flow meter on alarm relay YES (1) NO (0) YES (1) - IS-S
PA31
Type of humidifier alarm re-arm
0: Auto - Automatic
1: Manu - Manual
Auto (0) Auto (0) Manu (1) - IS-S
PA32 Humidifier alarm delay 2 0 999 Sec IS-S
PA33 Signal alarms humidifier on alarm relay YES (1) NO (0) YES (1) - IS-S
PA35
Type of anti-freeze alarm management:
0: Disabled
1: From digital contact
2: From anti-freeze probe
1 0 2 - IS-S
PA36 Alarm delay anti-freeze 5 0 999 Sec IS-S
PA37 Signal alarm anti-freeze on alarm delay YES (1) NO (0) YES (1) - IS-S
PA38
Activation Set Point for anti-freeze alarm from
transducer
2.0 PH03 PH04 °C IS-S
PA39
Activation differential for anti-freeze alarm from
transducer
3.0 0.0 10.0 °C IS-S
PA40 Enable RTC alarm YES (1) NO (0) YES (1) IS-S
PA41
Type of RTC alarm restoration
0: Auto - Automatic
1: Manu - Manual
Manu (1) Auto (0) Manu (1) - IS-S
PA42 Signal RTC alarms on alarm relay YES (1) NO (0) YES (1) - IS-S
PA45 Signal alarms fire/smoke on alarm relay YES (1) NO (0) YES (1) - IS-S
VARIOUS PARAMETERS
PH01
Minimum value threshold for the pressure
probe
0 -10.0 PH02 Bar IS-V
PH02
Maximum value threshold for the pressure
probe
30.0 PH01 45.0 Bar IS-V
PH03 Minimum temperature value for the Set Point -5.0 -15.0 PH04 °C IS-V
PH04 Maximum temperature value for the Set Point 40.0 PH03 70.0 °C IS-V
PH05
Enable machine start-up/shut-down by pressing
the ESC/Stand-By key
YES (1) NO (0) YES (1) - IS-V
PH06 Enable the change in summer/winter operating YES (1) NO (0) YES (1) - IS-V