C-PRO KILO AHU APPLICATION MANUAL
Pag. 37
PH52
Logistics of Digital inputs used for the alarm
flux status
NC (1) NO (0) NC (1) - IS-V
PH53 Logistics of Digital inputs for alarm fire-smoke NC (1) NO (0) NC (1) - IS-V
PH60 Logistics of alarm relay NO (0) NO (0) NC (1) - IS-V
PH15 Restoring the manufacturers’ defualt parameters NO (0) NO (0) YES (1) - IS-D
Wait for the
value NO(0)
upon
completion of
restore
PSd3 Password Installation Operator Level (3) 0 -999 9999 - IS
Level
4
CONSTRUCTOR MENU
CONFIGURATION PARAMETERS
Upon modification of these parameters it is
advised to remove and delete the card feed
PG00
Unit type:
1: Winter operating mode only
2: Summer operating mode only
3: Winter and summer operating mode with
humidity
4: Winter and summer operating mode with
humidity and heat recuperation
5: Two coils without dehumidification
6: Three coils with dehumidification
3 1 6 - CO-W
PG01
Number of coils
1: Heating/Cooling (Unit with single coil)
2: Heating, Cooling
3: Heating, Cooling, Post-Heating
1 1 3 - COW
If PG01=1 the
MOdE
parameter
decides if hot
or cold
PG02 Enable the presence of the expansion NO (0) NO (0) YES (1) - CO-W
PG03 Enable RTC system clock YES (1) NO (0) YES (1) - CO-W
If PG03=0,
history does
not memorize
elements and
the nocturnal
operating
mode is
disabled
PG04
Primary types of regulation:
0: On fan
1: On valves
Valv. (1) Fan (0) Valv. (1) - CO-W
PG05
Positioning probe of regulation:
0: Ambient probe
1: Probe in restart channel
Amb. (0) Amb. (0) Rest. (1) - CO-W
PG06
Enable humidifier
0: Disabled
1: Regulation ON-OFF
2: Regolation Modulating
1 0 2 - CO-W
PG07
Enabled external air shutters
0: Disabled
1: Modulating regulation
2: Fixed opening
1 0 2 - CO-W
PG08 Enable delivery fans YES (1) NO (0) YES (1) - CO-W
PG09 Enable pickup fans YES (1) NO (0) YES (1) - CO-W
PG10
Enable heating circulation pump (or single pump
for the unit at single coil)
NO (0) NO (0) YES (1) - CO-W
PG11 Enable cooling circulation pump NO (0) NO (0) YES (1)
- CO-W
PG12 Enable dehumidification NO (0) NO (0) YES (1)
- CO-W
PG13 Manage heating recuperator 0 0 4 - CO-W