Conn. Label Description
JA-1 AI1 Analogue input n.1 (for NTC probe)
JA-2 AI2 Analogue input n.2 (for NTC probe)
JA-3 AI3 Analogue input n.3 (for NTC probe)
JA-4 AI4 Analogue input n.4 (for NTC probe / transducers 0-20 mA /
transducers 4-20 mA); ratiometric transducers 0-5 V upon
request
JA-5 AI5 Analogue input n.5 (for NTC probe / transducers 0-20 mA /
transducers 4-20 mA); ratiometric transducers 0-5 V upon
request
JA-6 GND Common analogue inputs
JA-7 +5V Supplying power to ratiometric transducers
JA-8 +12V Supplying current to transducers
JB Connector for the digital signals
Conn. Label Description
JB-1 ID1 Digital input n.1
JB-2 ID2 Digital input n.2
JB-3 ID3 Digital input n.3
JB-4 ID4 Digital input n.4
JB-5 ID5 Digital input n.5
JB-6 ID6 Digital input n.6
JB-7 ID7 Digital input n.7
JB-8 GND Common digital inputs
JD: Connector for cut-phase output EVDFAN1 (analogue output 1)
Conn. Label Description
JD-1 VDC Supplying power to cut-phase module EVDFAN1
JD-2 AO1 Cut-phase module output EVDFAN1
In order to utilize the cut-phase module EVDFAN1, it is necessary to supply the expansion
with an alternate current; the phase which supplies power to the controller must be the same
as that which is supplied to both the expansion and the module.
JE: Connector for the analogue outputs 2 and 3 (for isolation); upon request, not available in
daytime models
Conn. Label Description (Version V+I)
JE-1 AO2 0-10VDC
JE-2 GND Common analogue outputs
JE-3 AO3 4-20mA
Description (Versione I+I)
JE-1 AO2 4-20 mA
JE-2 GND Common analogue outputs
JE-3 AO3 4-20 mA
Description (Versione V+V)
JE-1 AO2 0-10VDC
JE-2 GND Common analogue outputs
JE-3 AO3 0-10VDC