C-PRO KILO AHU APPLICATION MANUAL
Pag. 38
0: Disabled
1: At cross flow
2: Using two coils
3: Rotating On/Off (DO)
4: Rotating Modulating (AO)
PG14
Post-heating with electrical resistance:
0: Operation disabled
1: One stage of resistance
2: Two stages of resistance
3: Three stages of resistance
0 0 3 - CO-W
PSd4 Password for Constructor Level (4) 0 -999 9999 - CO
HARDWARE IN PARAMETERS
Hd01
Positioning of Digital inputs while machine is
On/Off
1 0 7 - CO-HI
Hd02
Positioning of Digital inputs for the changes in
operating mode (summer/winter)
0 0 7 - CO-HI
Hd03
Positioning of Digital inputs for the variations of
Set Point ambient
0 0 7 - CO-HI
Hd05
Positioning of Digital inputs of alarm thermal
delivery fan
3 0 7 - CO-HI
Hd06
Positioning of Digital inputs of alarm inverter
delivery fan
0 0 7 - CO-HI
Hd07
Positioning of Digital inputs of alarm thermal
pickup fan
0 0 7 - CO-HI
Hd08
Positioning of Digital inputs of alarm inverter
pickup fan
0 0 7 - CO-HI
Hd10
Position of digital input of thermal heating pump
alarm (or single circulation pump for the unit at
single coil)
0 0 14 - CO-HI
Hd11
Position of digital input of thermal cooling
pump alarm
0 0 14 - CO-HI
Hd13
Position of digital input of thermal resistance
pump alarm
0 0 14 - CO-HI
Hd15 Positioning of Digital inputs of alarm humidifier 0 0 7 - CO-HI
Hd16
Positioning of Digital inputs of alarm air
flowmeter
6 0 7 - CO-HI
Hd17
Positioning of Digital inputs of alarm anti-freeze
thermostat
5 0 7 - CO-HI
Hd18
Positioning of Digital inputs of alarm air filter
pressure switch
4 0 7 - CO-HI
Hd19
Position of digital input of pressure switch
recuperator alarm
0 0 14 - CO-HI
Hd20 Positioning of Digital inputs of alarm fire-smoke 0 0 7 - CO-HI
HARDWARE OUT PARAMETERS
HF01 Positioning of Digital outputs of delivery fans 1 0 7 - CO-HO
HF02 Positioning of Digital outputs of pickup fans 2 0 7 - CO-HO
HU01 Positioning of Digital outputs of humidifier 0 0 7 - CO-HO
HS01
Positioning of Digital outputs to control the
opening of external air shutters
4 0 7 - CO-HO
HS02
Positioning of Digital outputs to control the
closing of external air shutters
5 0 7 - CO-HO
HP01
Position of digital ouput of the heating pump (or
single circulation pump for the unit at single
coil)
0 0 14 - CO-HO
HP02 Position of digital output of the cooling pump 0 0 14 - CO-HO
Hr01
Position of the digital output dedicated to the
recuperator
0 0 14 - CO-HO
HE01
Position of the digital output of the first stage of
electrical resistance
0 0 14 - CO-HO