C-PRO KILO AHU APPLICATION MANUAL
Pag. 31
5.1 Directory of configuration parameters
Code
Description parameter Default Min Max UM Menu Note
CLOCK MENU
This menu is accessible only if PG03=1
PT01 Begin nocturnal operating mode 00:00:00 00:00:00 23:59:59 - OR
PT02 End nocturnal operating mode 00:00:00 00:00:00 23:59:59 - OR
PT03 Offset of Set Point nocturnal operating mode 0.0 -20.0 20.0 °C OR
Level
1
USER MENU
MOd
E
Operating mode
0: Summer (Cooling)
1: Winter (Heating)
1 0 1 - UT
SEtC Set Point summer 24.0 PH03 PH04 °C
SEtH Set Point winter/single 20.0 PH03 PH04 °C UT
If PH27=1
(single Set
Point), the
single Set
Point utilized
for regulation
and SEtH.
PU01 Set Point for humidity management 55 0 100 % UT
OS01 Offset at regulation Set Point from digital input 0.0 -20.0 20.0 °C UT If PH25=1
OS02 Offset at regulation Set Point from Supervisor 0.0 -20.0 20.0 °C UT If PH26=1
PSd1 Password for User Level (1) 0 -999 9999 - UT
Level
2
MAINTENANCE OPERATOR MENU
PM00
Limit the maximum hours of fan operation.
Related alarms will sound if maximum hours are
exceeded.
20000 0 100000 Hrs. MA-F
PM01 Hours of fan operation - delivery 0 0 100000 Hrs. MA-F
PM02 Hours of fan operation - pickup 0 0 100000 Hrs. MA-F
PM10
Limit the maximum hours of pump operation.
Related alarms will sound if maximum hours are
exceeded.
20000 0 100000 Hrs. MA-F
PM11 Hours of cooling pump operation 0 0 100000 Hrs. MA-F
PM12 Hours of heating pump operation 0 0 100000 Hrs. MA-F
PM90 Last date of machine maintenance - MA-F
PM20
Manual/automatic fan operation - delivery
0: Auto – automatic operation
1: Manu – manual operation
0 (Auto) 0 (Auto) 1 (Manu) - MA-M
PM21 Force the value of the fan in manual operation 0.0 0 100.0 % MA-M
If fan On/Off
set PM21>0 to
activate
PM23
Manual/automatic fan operation - pickup
0: Auto –automatic operation
1: Manu –manual operation
0 (Auto) 0 (Auto) 1 (Manu) - MA-M
PM24
Force the value of the fan pickup module in
manual operation
0.0 0 100.0 % MA-M
If fan On/Off
set PM24>0 to
activate
PM26
Manual/automatic humidifier operation
0: Auto –automatic operation
1: Manu –manual operation
0 (Auto) 0 (Auto) 1 (Manu) - MA-M
PM27
Force the value of the humidifier in manual
operation
0 0 100 % MA-M
If humidifier
On/Off set
PM27>0 to