C-PRO KILO AHU APPLICATION MANUAL
Pag. 34
PS09
Minimum variation regulation for operating the
external air shutters
0.0 0.0 90.0 % IS-SE
Enabled if
PS09>0
PS10 Fixed value for opening external air shutters 50.0 0.0 100.0 % IS-SE
Only with
fixed
regulation
(PG07=2)
PS11
Offset at Set Point during winter (at ambient
temp.) until the external air shutters remain
closed during winter operating mode
2.0 0.0 30.0 °C IS-SE
Only with
regulation
module
(PS01=1)
PS12
Differential enabling free-cooling and free-
heating in temperature
2.0 0.0 20.0 °C IS-SE
PS13
Differential Set Point enabling free-cooling and
free-heating in temperature
4.0 0.0 20.0 °C IS-SE
PS15
Differential enabling free-cooling and free-
heating heat exchanger
8.0 1.0 100.0
KJ/
Kg
IS-SE
PS16
Differential Set Point enabling free-cooling and
free-heating heat exchanger
10.0 1.0 200.0
KJ/
Kg
IS-SE
PS20 Set Point – Air Quality Control 600 0 10000 ppm IS-SE
PS21 Differential – Air Quality Control 100 0 2000 ppm IS-SE
RECUPERATORS
Menu accessible only if PG13>0
Pr01
Differential Set Point for regulation of
recuperator
5.0 0.0 20.0 °C IS-RH
Pr02 Differential of regulation of recuperator 3.0 0.0 20.0 °C IS-RH
Pr03 Minimum Set Point expulsion temperature 1.0 PH03 PH04 °C IS-RH
Pr04 Differential minimum expulsion temperature 4.0 0.0 20.0 °C IS-RH
Pr05
By pass cycle time of recuperators at cross flow
for melting
5 1 99 Min IS-RH
Pr07
Minimum velocity of rotating heat recuperator
velocity
0.0 0.0 Pr08 % IS-RH
Pr08
Maximum velocity of rotating heat recuperator
velocity
100.0 Pr07 100.0 % IS-RH
Only if
PG13=4
PUMPS
Menu accessibile only if PG10=1 or PG11=1
PP01
Types of pump regulation
0: Continuous regulation
1: Regulation On/Off
0 0 1 - IS-P
PP02
Set Point on the regulation ramp for pump
startup
5.0 PP03 90.0 % IS-P
PP03
Set Point on the regulation ramp for pump
shutdown
2.0 1.0 PP02 % IS-P
Only if
PP01=1
PP04
Wait time for pump shutdown (only with
PP01=1)
10 1 99 Min IS-P
OFF – Unit
immediately
shuts down
pump
HUMIDIFIER
This menu is accessible only if PG06=1
PU02
Type of regulation for humidifier
0: ON/OFF Regulation
1: Module Regulation
0 0 1 - IS-U
PU03 Differential for the regulation of the humidifier 10 0 100 % IS-U
PU10
Enable humidifier control with temperature of
delivery
YES (1) NO (0) YES (1) - IS-U
PU11
Set Point at temperature of delivery enabling
humidifier
22.0 PH03 PH04 °C IS-U
Only if
PU10=1
PU12
Differential on the temperature of delivery to
enable humidifier
3.0 0.0 20.0 °C IS-U
Only if
PU10=1
ALARM PARAMETERS