C-PRO MICRO SAVE APPLICATION MANUAL
Page 47
8 MODBUS VARIABLES
The controller can be managed by a supervisor via Modbus protocol. The communication takes
place via optional TTL/RS485 serial interface outside the controller. The various states/parameters
exported from the controller are shown below.
8.1 ModBus exporting table
Addr
Base 0
Addr
Base
1
Name Value Min Max Description Mode
0x0100 257 Packed_DI 0 0 65535
Bit1=DI1, Bit2=DI2,
Bit3=DI3, ...,
Bit13=DI13,
Bit14=DI14
R/W
0x0180 385 Packed_DO 0 0 65535
Bit1=DO1,
Bit2=DO2, ...,
Bit13=DO13,
Bit14=DO14
R/W
0x0200 513 AI01_Antireeze_Probe 0.0 -3276.8 3276.7 R/O
0x0201 514 AI02_AirSupply_Probe 0.0 -3276.8 3276.7 R/O
0x0202 515 AI03_AirReturn_Probe 0.0 -3276.8 3276.7 R/O
0x0203 516 AI04_CO2_Probe 0 -32768 32767 R/O
0x0204 517 AI05_AirExternal_Probe 0.0 -3276.8 3276.7
Only Complete
Version
R/O
0x0281 642 AO_ByPassRecover 0.00 0.00 100.00 R/W
0x0282 643 inverterFan_Return 0.00 0.00 100.00 R/W
0x0283 644 inverterFan_Supply 0.00 0.00 100.00 R/W
0x0284 645 AO_HeatingCoilRequest 0.00 0.00 100.00
Only Complete
Version
R/W
0x0300 769 PackedAlarm_1 0 0 65535
Bit1=AL01,
Bit2=AL02,
Bit3=AL03,
Bit4=AL04,
Bit5=AL05,
Bit6=AL06,
Bit7=AL07,
Bit8=free,
Bit9=AL09,
Bit10=AL10,
Bit11=AL11,
Bit12=AL12,
Bit13=AL13,
Bit14=AL14,
Bit15=AL15,
Bit16=AL16
R/W
0x0301 770 PackedAlarm_2 0 0 65535
Bit1=AL17,
Bit2=AL18,
Bit3=AL19,
R/W