C-PRO MICRO SAVE APPLICATION MANUAL
Page 45
7.2 Alarms table
Below is a list of all alarms managed by the application. The order of presentation is the same as the
order of active alarms occurrence. The alarms can be displayed also with the machine in OFF status.
Code Alarm description Reset Consequence Delay
AL01 Supply fan thermal overload
(*1)
Automatic
Switches all devices off Fixed 2 s
AL02 Return fan thermal overload
(*1)
Automatic
Switches all devices off Fixed 2 s
AL03 Differential pressure switch
(*1)
Manual
Switches all devices off Selectable
AL04 Hot water coil anti-freeze Automatic
- Open the hot water valve
completely
- Close the fresh air damper
- Switches fans OFF
Selectable
AL05
Electric heaters thermal overload – manual
reset
Manual Switches the heaters OFF Fixed 2 s
Outside air damper limit switch “completely
open”
(*1)
AL06
Outside air damper limit switch “completely
closed”
(*1)
Manual Switches all devices off Selectable
AL07
Electric heaters thermal overload – automatic
reset
Automatic Switches the heaters OFF Selectable
AL09 Supply fan running hours Manual
(*2)
Signalling only -
AL10 Return fan running hours Manual
(*2)
Signalling only -
AL11 Anti-freeze temperature probe Automatic Inhibits the relevant control Selectable
AL12 Supply air temperature probe Automatic Inhibits the relevant control
Selectable
AL13 Return air temperature probe Automatic Inhibits the relevant control
Selectable
AL14 CO
2
probe Automatic Inhibits the relevant control
Selectable
AL15 Outdoor intake air temperature probe Automatic Inhibits the relevant control
Selectable
AL16 RTC broken or battery discharged alarm Manual
Inhibits the control depending on
RTC
-
AL17 Expansion communication alarm Automatic
Switches OFF the devices
connected to the expansion
-
(
*1
) These alarms cause the unit to switch OFF (OFF due to alarm status)
(
*2
) To reset the alarms linked to running hours just reset the device hours.
7.3 General alarm relay
The controller manages a configurable alarm relay. For each alarm there is a parameter which
selects whether that alarm must be signalled on the alarm relay. Several alarms can be addressed to
the relay.
Via the relevant parameter (PH61) it is possible to establish the polarity (NO, or NC) of the alarm
relay.