C-PRO MICRO SAVE APPLICATION MANUAL
Page 31
Code Parameter description Default Min Max UM Menu Notes
FANS
PF06
Minimum time that must pass for the switch-
on/off of each individual step of the fans
3 0 999 Sec CO-F
PF07
Fans temperature setpoint for anti-freeze
protection of the recovery heat exchanger
2.0 PH01 PH02
°C
°F
CO-F
PF08
Fans differential for anti-freeze protection of
the recovery heat exchanger
2.0
0.0
0.0
20.0
36.0
°C
°F
CO-F
PF09
Minimum stand-by time before requesting
switch-off of a further fan step
5 1 99 Min CO-F
PF10
Fans differential regulation for the by-pass of
the recovery unit damper in anti-freeze
protection mode
2.0
0.0
0.0
20.0
36.0
°C
°F
CO-F
PF11
Fans functioning time in post-ventilation
mode
30 0 999 Sec CO-F
HEATING COILS
This menu is only accessible if PG02>0
Pb02
Proportional band for PI regulation of the
heating coil (water/electric)
10.0
0.0
0.0
20.0
36.0
°C
°F
CO-B
Pb03
Integral time for PI regulation of the heating
coil (water/electric)
0 0 999 Sec CO-B
If Pb03=0
integral action
not present
Pb04
Hot water coil opening value in regulation
probe error mode
0.0 0.0 100.0 % CO-B
Pb05
Heaters single stage insertion/release time for
post-heating
60 0 999 Sec CO-B
Pb06
Number of electric heaters active during
probe error mode.
1 0 3 CO-B
OUTSIDE AIR DAMPER
This menu is only accessible if PG04=1
PS01
Fans switch-on delay from outside air damper
activation
45 0 999 Sec CO-SE
PS02
Outside air damper switch-on delay from fans
switch-off
15 0 999 Sec CO-SE
PS05 Delay of outside air damper end run 60 0 999 Sec CO-SE
RECOVERY HEAT EXCHANGER
Pr01 Anti-freeze temperature minimum setpoint 1.0 PH01 PH02
°C
°F
CO-RH
Pr02 Anti-freeze temperature minimum differential 2.0
0.0
0.0
20.0
36.0
°C
°F
CO-RH
Pr03
Recovery heat exchanger by-pass cycle time
for cyclical defrosting
5 1 99 Min CO-RH
Used only if
PG06=2
Vista de pagina 30