C-PRO MICRO SAVE APPLICATION MANUAL
Page 25
Code Parameter description Default Min Max UM Menu Notes
MAINTENANCE
PM01
Max number of fans working hours. The
relevant alarm occurs over this limit
20000 0 100000 Hours IS-MA
PM02 Supply fan working hours 0 0 100000 Hours IS-MA
PM03 Return fan working hours 0 0 100000 Hours IS-MA
PM90 Last maintenance date IS-MA
PM11 Anti-freeze air temperature probe offset
0.0
0.0
-10.0
-18.0
10.0
18.0
°C
°F
IS-MA
FANS
PF01
Type of fans regulation:
0: Manual
1: Automatic
2: Automatic with presence sensor
0 0 2 IS-F
PF03 Fans speed in COMFORT period V2 V0 V3 IS-F
PF04 Fans speed in ECONOMY period V1 V0 V3 IS-F
PF05 Fans speed in RTC error V0 V0 V3 IS-F
Only if
PF01=1/2 /3
PF12
Fans speed in COMFORT with presence
sensor active
V3 V1 V3 IS-F
PF13 Speed in case of « non Working » day V0 V0 V3 IS-F
PF21 Speed variator value corresponding to speed V1 33.50 0.00 100.00 % IS-F
PF22 Speed variator value corresponding to speed V2 66.50 0.00 100.00 % IS-F
PF23 Speed variator value corresponding to speed V3 100.00 0.00 100.00 % IS-F
Only version
with variator
ALARM PARAMETERS
PA01 Enabling fans working hours alarm
Active
(1)
Not-active
(0)
Active (1) - IS-S
PA02
Signals working hours alarms on alarm
relay
No (0) No (0) Yes (1) - IS-S
PA04
Signals the supply/return fans thermal
overload on the alarm relay
Yes (1) No (0) Yes (1) - IS-S
PA25 Signals RTC alarm on alarm relay Yes (1) No (0) Yes (1) - IS-S
PA27 Signals probe alarms on alarm relay Yes (1) No (0) Yes (1) - IS-S
VARIOUS PARAMETERS
PH01 Minimum temperature value -15.0
-20.0
-4.0
PH02
°C
°F
IS-V
PH02 Maximum temperature value 95.0 PH01
110.0
230.0
°C
°F
IS-V
PH05
Enables unit switch-on/off from
"Start/Stop" digital input
Yes (1) No (0) Yes (1) - IS-V
PH06 Enables unit switch-on/off from supervisor No (0) No (0) Yes (1) IS-V
PH18 Cancels the alarms log NO (0) NO (0) YES (1) - IS-V
Set Yes (1)
ad wait for
the NO (0)
value to be
read again
PH20 Enable buzzer Yes (1) No (0) Yes (1) - IS-V
PH30
Temperature unit of measurement
0: °Celsius
1: °Fahrenheit
0 (°C) 0 (°C) 1 (°F) - IS-V
PH99 Reset the factory parameters default NO (0) NO (0) YES (1) - IS-D
Wait for the
NO (0)
value to be
read again
on reset
completion
PSd2 Installer level password (2) 0 -999 9999 - IS