C-PRO MICRO SAVE APPLICATION MANUAL
Page 30
Code Parameter description Default Min Max UM Menu Notes
VARIOUS PARAMETERS
PH01 Minimum temperature value -15.0
-20.0
-4.0
PH02
°C
°F
IS-V
PH02 Maximum temperature value 95.0 PH01
110.0
230.0
°C
°F
IS-V
PH03 Minimum CO
2
probe PPM value 0 0 PH04 ppm IS-V
PH04 Maximum CO
2
probe PPM value 0 PH03 10000 ppm IS-V
PH05
Enables unit switch-on/off from
“Start/Stop” digital input
Yes (1) No (0) Yes (1) - IS-V
PH06 Enables unit switch-on/off from supervisor No (0) No (0) Yes (1) IS-V
PH18 Cancels the alarms log NO (0) NO (0) YES (1) - IS-V
Set YES (1)
ad wait for
the NO (0)
value to be
read again
PH20 Enable buzzer Yes (1) No (0) Yes (1) - IS-V
PH30
Temperature unit of measurement
0: °Celsius
1: °Fahrenheit
0 (°C) 0 (°C) 1 (°F) - IS-V
PH99 Reset the factory parameters default NO (0) NO (0) YES (1) - IS-D
Wait for the
NO (0)
value to be
read again
on reset
completion
PSd2 Installer level password (2) 0 -999 9999 - IS
Level 3 MANUFACTURER MENU
CONFIGURATION PARAMETERS
After modification of these parameters it is recommended to remove and then re-apply the power supply to the board.
PG01 Enabling of expansion Yes (1) No (0) Yes (1) - CO-G
PG02
Selection of type of device for heating:
0: Disabled
1: Hot water coil only
2: Electric heater coil only
Heaters
(2)
Disabled
(0)
Heaters
(2)
- CO-G
PG03
Type of recovery heat exchanger by-pass
damper control:
0: Digital Control (DO7)
1: Analogue Control (AO3)
DO (0) DO (0) AO (1) - CO-G
PG04 Outside air damper enabling Yes (1) No (0) Yes (1) - CO-G
PG05 Enabling of post-ventilation Yes (1) No (0) Yes (1) - CO-G
PG06
Enabling of recovery heat exchanger anti-
freeze protection
Type 1
(1)
Disabled
(0)
Type 2
(2)
- CO-G
PG08
Enabling of recovery heat exchanger by-pass
in summer
Yes (1) No (0) Yes (1) CO-G
PG09 Activation of outside air damper end run Yes (1) No (0) Yes (1) CO-G
PG10 Type of fan DO (0) DO (0) AO (1) - CO-G
PSd1 User level password (1) 0 -999 9999 - CO-G
PSd2 Installer level password (2) 0 -999 9999 - CO-G
PSd3 Manufacturer level password (3) 0 -999 9999 - CO-G