5.2 COMPLETE solution list of configuration parameters
Code Parameter description Default Min Max UM Menu Notes
Level 1 USER MENU
USER
SPHM Supply temperature heating setpoint 22.0 PH01 PH02
°C
°F
UT
SPHR Return temperature heating setpoint 20.0 PH01 PH02
°C
°F
UT
PF02 Fans speed in manual regulation mode V3 V0 V3 UT
Only if
PF01=0
(Manual
Regulation)
PSd1 User level password (1) 0 -999 9999 - UT
Level 2 INSTALLER MENU
CLOCK
PT01 Start of the COMFORT time period 10:00:00 00:00:00 23:59:59 - OR
PT02 Start of the ECONOMY time period 16:00:00 00:00:00 23:59:59 - OR
PT11 Sunday
0
Working
0
Working
1
Not Working
OR
PT12 Monday
0
Working
0
Working
1
Not Working
OR
PT13 Tuesday
0
Working
0
Working
1
Not Working
OR
PT14 Wednesday
0
Working
0
Working
1
Not Working
OR
PT15 Thursday
0
Working
0
Working
1
Not Working
OR
PT16 Friday
0
Working
0
Working
1
Not Working
OR
PT17 Saturday
0
Working
0
Working
1
Not Working
OR
MAINTENANCE
PM01
Functioning hours maximum limit for fans.
The relevant alarm will be triggered over
this limit
8000 0 100000 Hours IS-MA
PM02 Outlet fan functioning hours 0 0 100000 Hours IS-MA
PM03 Return fan functioning hours 0 0 100000 Hours IS-MA
PM90
Last date on which maintenance was
performed on the machine
IS-MA
PM11
Calibration of the anti-freeze air
temperature probe
0.0
-10.0
-18.0
10.0
18.0
°C
°F
IS-MA
PM12
Calibration of the outlet air temperature
probe
0.0
-10.0
-18.0
10.0
18.0
°C
°F
IS-MA
PM13
Calibration of the return air temperature
probe
0.0
-10.0
-18.0
10.0
18.0
°C
°F
IS-MA
PM15
Calibration of the outside air introduction
temperature probe
0.0
-10.0
-18.0
10.0
18.0
°C
°F
IS-MA