C-PRO MICRO SAVE APPLICATION MANUAL
Page 26
Code Parameter description Default Min Max UM Menu Notes
Level 3 MANUFACTURER MENU
CONFIGURATION PARAMETERS
After modification of these parameters it is recommended to remove and then re-apply the power supply to the board.
PG01 Enabling of expansion No (1) No (0) Yes (1) - CO-G
PG02
Selection of type of device for heating:
0: Disabled
1: Hot water coil only
2: Electric heater coil only
Disabled
(0)
Disabled
(0)
Heaters
(2)
- CO-G
PG03
Type of recovery heat exchanger by-pass
damper control:
0: Digital Control (DO7)
1: Analogue Control (AO3)
AO (1) DO (0) AO (1) - CO-G
PG04 Outside air damper enabling No (0) No (0) Yes (1) - CO-G
PG05 Enabling of post-ventilation No (0) No (0) Yes (1) - CO-G
PG06
Enabling of recovery heat exchanger anti-
freeze protection
Type 1
(1)
Not-active
(0)
Type 2 (2) - CO-G
PG08
Enabling of recovery heat exchanger by-
pass in summer
No (0) No (0) Yes (1) CO-G
PG09 Activation of outside air damper limit switch No (0) No (0) Yes (1) CO-G
PG10 Type of fan DO (0) DO (0) AO (1) - CO-G
PSd1 User level password (1) 0 -999 9999 - CO-G
PSd2 Installer level password (2) 0 -999 9999 - CO-G
PSd3 Manufacturer level password (3) 0 -999 9999 - CO-G
FANS
PF06
Minimum time that must pass for the switch-
on/off of each individual step of the fans
3 0 999 Sec CO-F
PF07
Temperature setpoint of the fans for anti-
freeze protection of the recovery heat
exchanger
2.0 PH01 PH02
°C
°F
CO-F
PF08
Differential for anti-freeze protection of
the recovery heat exchanger
2.0 0.0
20.0
36.0
°C
°F
CO-F
PF09
Minimum stand-by time before requesting
switch-off of a further fan step
5 1 99 Min CO-F
PF10
Differential for the by-pass of the recovery
unit damper in anti-freeze protection mode
2.0 0.0
20.0
36.0
°C
°F
CO-F
PF11
Fans working time in post-ventilation
mode
30 0 999 Sec CO-F
OUTSIDE AIR DAMPER
This menu is only accessible if PG04=1
PS01
Fans switch-on delay from outside air
damper activation
45 0 999 Sec CO-SE Reading only
PS02
Outside air damper switch-OFF delay from
fans switch-off
15 0 999 Sec CO-SE
PS05 Delay of outside air damper end run 60 0 999 Sec CO-SE
RECOVERY HEAT EXCHANGER
Pr01 Anti-freeze temperature minimum setpoint 1.0 PH01 PH02
°C
°F
CO-RH
Pr02
Anti-freeze temperature minimum
differential
2.0 0.0
20.0
36.0
°C
°F
CO-RH
Pr03
Recovery heat exchanger by-pass cycle
time for cyclical defrosting
5 1 99 Min CO-RH