EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324
page 61 of 116
Parameters (1) AI3 - - - - - - - - - NTC
kind of probe analog input 3
PTC = PTC probe
NTC = NTC probe
0-20mA = 0-20 mA transducer
4-20mA = 4-20 mA transducer
0-5V = 0-5 V ratiometric transducer
0-10V = 0-10 V ratiometric transducer
PT1000 = Pt 1000 probe
Parameters (1) AI Err Time 0 240 s 2
analog inputs time-out (after this time without
communication with an analog input, the
controller signals the analog input error)
Parameters (1) AO1 - - - - - - - - - PWM
kind of signal analog input 1
PWM = PWM (Pulse With Modulation)
Parameters (1) AO2 - - - - - - - - - 0-10V
kind of signal analog input 2
0-20mA = 0-20 mA
4-20mA = 4-20 mA
0-10V = 0-10 V
Parameters (1) AO3 - - - - - - - - - 0-10V
kind of signal analog input 3
0-20mA = 0-20 mA
4-20mA = 4-20 mA
0-10V = 0-10 V
Parameters (1) CosPhi 10us - - - - - - - - - - - - reserved
Parameters (2)
[ press button
RIGHT to
show it ]
I/O Timeout 1 240 s 60
time-out of the CANbus communication for
the test of the remote values of the I / O
(after this time without CANbus
communication, the I / O of the controller is
disabled)
Parameters (2)
[ press button
RIGHT to
show it ]
En. Prg Level - - - - - - - - - NO
enabling the access to the first level page
pressing a combination of buttons
YES = yes, operating as follows:
- keep pressed 3 s button
ENTER to gain access
to the first page of
level 1
- keep pressed 3 s
buttons ENTER and
ESC to gain access to
the first page of level 2
- keep pressed 3 s
buttons LEFT and
RIGHT to gain access to
the first page of level 3