EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324
page 109 of 116
NTC analog inputs (10K Ω @ 25 °C, 77 °F)
Kind of sensor: NTC 2.
Working range: from -40 to 86 °C (-40 to 186 °F).
Accuracy: ±1 °C.
Resolution: 0.1 °C.
Conversion time: 100 ms.
Protection: no protection.
NTC analog inputs (10K Ω @ 25 °C, 77 °F)
Kind of sensor: NTC 2.
Working range: from -40 to 86 °C (-40 to 186 °F).
Accuracy: ±0.7% of the full scale between -40 and 100 °C, ±1 °C
between -50 to -40 °C and between 100 and 120 °C .
Resolution: 0.1 °C.
Conversion time: 100 ms.
Protection: no protection.
Pt 1000 analog inputs (1K Ω @ 0 °C, 32 °F)
Working range: from -100 to 400 °C (-148 to 752 °F ).
Accuracy: ±0.5% of the full scale.
Resolution: 0.1 °C.
Conversion time: 100 ms.
Protection: no protection.
0-20 mA / 4-20 mA analog inputs
Input resistance: ≤ to 200 Ω.
Accuracy: ±0.5% of the full scale.
Resolution: 0.01 mA.
Conversion time: 100 ms.
Protection: no protection; the maximum current allowed on each input is
25 mA.
0-5 V ratiometric / 0-10 V analog inputs
Input resistance: ≥ to 10K Ω.
Accuracy: ±0.5% of the full scale.
Resolution: 0.01 V.
Conversion time: 100 ms.
Protection: against the reversal of the polarity.
Digital inputs:
c-pro 3 hecto
c-pro 3 mega and c-pro 3
NODE mega
c-pro 3 EXP hecto
5 non optoisolated free of
voltage digital inputs.
7 optoisolated digital inputs
at 24 VAC / DC.
5 non optoisolated free of
voltage digital inputs.
c-pro 3 hecto+ c-pro 3 mega+ c-pro 3 EXP hecto+