0x0691
1682 PF17_Ti 0 0 300 R/W
0x0692
1683 PF30_MinSpeedFan 0.00 0.00 100.00 PF03 - Min speed fan R/W
0x0693
1684 PF31_MaxSpeedFan 100.00 0.00 100.00 PF04 - Max speed fan R/W
0x0694
1685 PF32_StaticPressSetPointRamp 300 0 30000 R/W
0x0695
1686 PF33_StaticPressSetPoint1 300 0 30000 R/W
0x0696
1687 PF34_StaticPressSetPoint2 400 0 30000 R/W
0x0697
1688 PF35_StaticPressSetPoint3 500 0 30000 R/W
0x0698
1689 PF36_StaticPressPropBand 200 0 10000 R/W
0x0699
1690 PF37_StaticPressIntegralTime 0 0 300 R/W
0x069A
1691 PF38_ForceOnErrorProbe 30.00 0.00 100.00 R/W
0x069B
1692 PG11_Recyclage 0 0 1 0=Disable, 1=Enable R/W
0x069C
1693 PS06_EnableFreeHeating 0 0 1 0=Disable, 1=Enable R/W
0x069D
1694 PS07_Type_ControlShutter 0 0 4
0=FreeCooling/Heating,
1=AirQuality,
2=Greater 3=Avarage
4=Fixed
R/W
0x069E
1695 PS08_MinRegulationValue_AirExternalShutter 20.00 0.00 100.00
R/W
0x069F
1696 PS09_MaxRegulationValue_AirExternalShutter
100.00 0.00 100.00
R/W
0x06A0
1697 PS10_FixRegulationValue_AirExternalShutter 50.00 0.00 100.00
R/W
0x06A1
1698 PS12_FreeCoolingHeatingTemp_enDiff 2.0 0.0 36.0
R/W
0x06A2
1699 PS13_FreeCoolingHeatingTemp_enSetPoint 4.0 0.0 68.0
R/W
0x06A3
1700 PS15_EnableMinVal_AirExternalShutter 0 0 2
0=Disable, 1=Only
Band, 2=Always
R/W
0x06A4
1701 PS20_AirQuality_SetPoint 600 0 10000
R/W
0x06A5
1702 PS21_AirQuality_Diff 100 0 2000
R/W
Vista de pagina 65