C-PRO MEGA HARDWARE MANUAL
Page 27
Note:
1) baud rate selectable by two jumpers
2) The CAN connection consists of a cable with twisted pair (both
shielded and not shielded). The first and the last elements of the
system must have the bus terminating resistor connected (impedance
is 120
). A second twisted pair is used for the feed and the ground
Number 1
type RS485, optoinsulated
Physical layer 2 wires + common wire
Baud rate (max. length 1000 m) 1200 - 19200
Connector Disconnectable screw
terminals
type RS232, optoinsulated
Physical layer Tx, Rx + 2 signals for
modem control + common
wire
Baud rate (max. length 3 m) 1200 - 19200
Connector Disconnectable screw
terminals
RS485 serial
communication
(UART1)
Note:
1) baud rate is selectable by parameters
2) The CAN connection consists of a cable with twisted pair (both
shielded and not shielded). The first and the last elements of the
system must have the bus terminating resistor connected (impedance
is 120
). A second twisted pair is used for the feed and the ground
Number 1
Backup type Supercap
RTC
(Real Time Clock)
RTC data retention time in the event of a
power failure
3 days
Buzzer Number
1
Signaling LEDs Number 6
The open case version of the controller is available with the fixed screw terminals only.