EVCO S.p.A. EVF 300 series | Installer manual ver. 1.1 | Code 144F300E114
Page 15 of 62
5 COMMISSIONING
5.1 Commissioning
Operate as indicated:
1. Install the device using the methods illustrated in the 2 “DIMENSIONS AND INSTALLATION” chapter, following all warnings
given in the 3.2 “Installation warnings” paragraph.
2. Connect the device electrically using the methods illustrated in the 3 “ELECTRIC CONNECTION” chapter, following all
warnings given in the 3.2 “Warning for electric connection” paragraph, without connecting the power supply and the mains
electricity.
3. Connect the device power supply: an internal test will be started.
The test typically requires a few seconds.
4. If, at the conclusion of the test, a display shows flashing “rtc” and the device emits an intermittent sound, the day of the
week and the time must be set; see paragraph 14.1 “Setting the day of the week and time”.
5. Configure the device with the procedure illustrated in paragraph 14.5 “Setting
the configuration parametersthe
configuration parameters”.
The following table illustrates the meaning of the configuration parameters; the parameters are listed with the order,
according to which, it is appropriate that the device is configured.
PARAM. MEANING FACTORY SETTING
CFG
type of operation
0 = with one analogue input (chamber probe, i.e. with management of the
power supplied at the top and at the floor independently from each
other.)
1 = with two analogue inputs (top and floor probe, i.e. with management of
the temperature of the top and at the floor independently from each
other.)
0
P0
probe type
0 = thermocouple J
1 = thermocouple K
0
P2
unit of measurement
0 = °C
1 = °F
0
SP work set-point (visible only if the CFG parameter is set at 0) 150 °C
SP1 top set-point (visible only if the CFG parameter is set at 1) 150 °C
SP2 floor set-point (visible only if the CFG parameter is set at 1) 150 °C
Po1 power distributed at top (visible only if the CFG parameter is set at 0) 50 %
Po2 power distributed at floor (visible only if the CFG parameter is set at 0) 50 %
u1
utility managed by the digital output K4
0 = extraction hood
1 = multifunction
0