CONFIGURATION PARAMETERS (1/2)
NOTE CODE PARAMETER DESCRIPTION MIN. MAX. U.M. STAND.
(1) PA password -55 99 --- ---
/ MEASURE INPUTS
(1) /1 calibration (ref. to the cabinet probe) -10 +10 °C0
c QUICK-COOLING/FREEZING AND COLD-STORING ON-OFF REGULATOR
(1) c0 hysteresis (differential, ref. to the cabinet probe) +1 +15 °C+2
(1) c1 maximum length of the quick-cooling for temperature 1 400 min. 90
(1) c2 quick-cooling for temperature cut off set (ref. to the needle probe) -55 +99 °C +10
(1) c3 cold-storing set (ref. to the cabinet probe) -55 +99 °C+3
(1) c4 maximum length of the quick-freezing for temperature 1 400 min. 270
(1) c5 quick-freezing for temperature cut off set (ref. to the needle probe) -55 +99 °C -18
(1) c6 very cold-storing set (ref. to the cabinet probe) -55 +99 °C -25
c7 threshold for needle probe properly positioned fast-test 0 +99 °C +30
(1) c8 quick-cooling/freezing for temperature enabling set (ref. to the needle probe) -55 +99 °C +65
c9 alarm buzzer activation length when a quick-cooling/freezing ends 0 99 sec. 3
(1)(2) cA needle probe reading --- --- °C ---
(1) cb quick-cooling working set (ref. to the cabinet probe) -55 +99 °C -10
(1) cC quick-freezing working set (ref. to the cabinet probe) -55 +99 °C -55
(1) cd Hard-phase cut off set (ref. to the needle probe) -55 +99 °C -15
cE during of the needle probe properly positioned differential-test 1 99 sec. 255
(1) cF Hard-phase working set (ref. to the cabinet probe) -55 +99 °C +15
t HARD-PHASE DURING A QUICK-COOLING FOR TIME
C0 Hard-phase during 1 400 min. 60
C COMPRESSOR OUTPUT PROTECTIONS
C0 disabling time at the output activation from the instrument start 0 99 min. 0
C1 disabling time at the output activation from the preceding activation 0 99 min. 0
C2 disabling time at the output activation from the preceding deactivation 0 99 min. 0
C5 cycle time for the output activation in case of cabinet probe failure 0 99 min. 10
C6 output activation length during the cold-storing in case of cabinet probe failure 0 99 min. 3
C7 output activation length during the very cold-storing in case of cabinet probe failure 0 99 min. 8
d DEFROST REGULATOR
(3) d0 defrost interval 0 99 hours/min. 8
(4) d1 kind of defrost 0 2 --- 1
d2 defrost cut off set (ref. to the evaporator probe) -55 +99 °C+2
d3 maximum defrost length 1 99 min./sec. 30
d5 first defrost intervall from the begin of the cold-storing phase 0 99 min. 0
d 4 defrost at the beginning of the quick-cooling/freezing 0=NO; 1=YES 0 1 --- 0
d7 dripping length 0 99 min./sec. 2
(5) d9 forced defrost (delays override) 0 1 --- 0
(1)(2) dA evaporator probe reading --- --- °C ---
(6) db times base for the parameters d0, d3, d7 and F5 0 1 --- 0
F EVAPORATOR FANS REGULATOR
(7) F0 output activity 0 1 --- 0
F1 output deactivation set (ref. to the evaporator probe) -55 +99 °C-1
F2 hysteresis (differential, ref. to the evaporator probe) +1 +15 °C+1
F 3 output deactivated if the compressor is deactivated 0=NO; 1=YES 0 1 --- 1
F4 output deactivated during the defrost 0=NO; 1=YES 0 1 --- 1
F5 disabling time at the output activation from the end of the dripping 0 99 min./sec. 3
u DIGITAL INPUTS
(8) u0 door-switch activate cabinet light output 0=NO; 1=YES 0 1 --- 1