Evco S.p.A. Vgraph | Hardware manual ver. 1.01 | Code 114VGRAHWE01
page 13 of 22
CAN Network MyNode 1 127 - - - 99 Local (or of the interface) CAN node’s address
CAN Network Master - - - - - - - - - YES The interface always works as master
CAN Network Baud - - - - - - - - - Auto
CAN communication baud rate
20K = 20,000 baud
50K = 50,000 baud
125K = 125,000 baud
500K = 500.000 baud
Auto = the interface recognizes the baud
rate automatically, on condition
that it is one of the those
mentioned above
CAN Network Net Timeout 1 240 s 5
Remote (or of the devices in the network) CAN
communication time-out (after this time without
CAN communication with a device, this will be
excluded by the network)
CAN Network NW Node [1] 1 [32] 127 - - - - - -
Remote (or of the devices in the network) CAN
nodes’ address; example for [1] 2:
[1] = node
2 = node’s address
Modbus Address 1 247 - - - 1 Modbus address (reserved)
Modbus Parity - - - - - - - - - even
Modbus communication parity (reserved)
none = no parity
odd = odd
even = even
Modbus Baudrate - - - - - - - - - 9600
Modbus communication baud rate (reserved)
1200 = 1,200 baud
2400 = 2,400 baud
4800 = 4,800 baud
9600 = 9,600 baud
19200 = 19,200 baud
28800 = 28,800 baud
38400 = 38,400 baud
57600 = 57,600 baud
Modbus Bit Stop - - - - - - - - - 1 bit
Modbus communication stop bit number
(reserved)