7.7.5 Configuration parameters of the submenu “UART” of the menu “Networks
The following table shows the meaning of the configuration parameters of the submenu “UART” of the menu “Networks”.
PARAM. MIN. MAX. U.M. DEF. DESCRIPTION
Address 1 247 - - - 1
MODBUS address of the device (meaningful if the communication
protocol is MODBUS slave)
Parity - - - - - - - - - even
parity of the MODBUS communication
none = none
odd = odd
even = even
Baudrate - - - - - - - - - 9600
baud rate of the MODBUS communication
1200 = 1,200 baud
2400 = 2,400 baud
4800 = 4,800 baud
9600 = 9,600 baud
19200 = 19,200 baud
28800 = 28,800 baud
38400 = 38,400 baud
57600 = 57,600 baud
Bit Stop - - - - - - - - - 1 bit
number of stop bit of the MODBUS communication
1 bit = 1 bit
2 bit = 2 bit
Timeout 2 240 s 10
time-out of the local MODBUS communication, or of the device
(once the time you have set with this parameter has elapsed from
the transmission of a request without answer, the transmission of
the request is considered failed and the following request is
transmitted; meaningful if the communication protocol is
MODBUS master)
7.7.6 Configuration parameters of the submenu “USB” of the menu “Networks”
The following table shows the meaning of the configuration parameters of the submenu “USB” of the menu “Networks”.
PARAM. MIN. MAX. U.M. DEF. DESCRIPTION
USB Status
Device
parameter available in read only mode reserved
Device
Status Idle
Speed
parameter available in read only mode reserved