5
PRODUCTS LINE '96
CODE PARAMETER DESCRIPTION MIN. MAX. U.M. ST.
(1) PA Password -99 100 ---- ----
/ PROBE
/0 kind of probe 10="J" TC; 11="K" TC 10 11 ---- *
(1) /1 calibration (measure offset) -10 +10 °C0
/2 digital filter (speed response) 0=0s; 1=0,4s; 2=1,2s; 3=2,8s; 4=6,0s; 5=12,4s; 6=25,2s 0 6 ---- 3
r TEMPERATURE REGULATOR
r1 minimum setpoint admitted 0 +999 °C0
r2 maximum setpoint admitted 0 +999 °C (2)
P P.I.D. REGULATOR
P0 offset band -99 +99 °C0
PI integral time 0 999 sec. 100
P2 Auto-tuning enabling 0=NO; 1=YES 0 1 ---- 1
Pb proportional band +1 +250 °C +30
Pc P.I.D. cycle time 1 120 sec. 30
Pd derivative time 0 250 sec. 35
A ALARM
A0 alarm hysteresis (differential) +1 +99 °C+1
A1 alarm setpoint -99 +999 °C0
A3 alarm disabling time since instrument power-on 0 999 min. 0
A4 alarm mode see TABLE 1
L NETWORK CONNECTION
L1 instrument address 1 15 ---- 1
L2 instrument group 0 7 ---- 0
L3 time-out link 2 250 sec. 7
L4 baud rate 0 3 baud 1
CONFIGURATION PARAMETERS
TABLE
parameter A4 alarm mode
1 disabled
2 absolute minimum alarm
3 absolute maximum alarm
4 minimum alarm relative to setpoint
5 maximum alarm relative to setpoint
6 minimum alarm relative to setpoint
with automatic enabling and recompute
7 maximum alarm relative to setpoint
with automatic enabling and recompute
NOTES
(*) = depends on the kind of probe.
(1) = configuration parameter present on Level 1.
(2) = for "J" thermocouples r2 = 700 °C; for "K" thermocouples r2 = 999 °C.