4 List of Parameters
The same parameters organisation used for c-pro CHILL can be maintained.
For the parameters and functions of the c-pro HPR0 application, see the following table.
As an example, the codes used with CHIL have been maintained (that will appear on the LED
display), but which will be “re-organised” regarding numbering depending on this new application.
Code
Parameter description Default Min Max U.M. Menu Notes
USER PARAMETERS
PSd1 Modify the password to User level 0 -999 9999 UT
OUTLET SET
SPC1
Sets the summer outlet setpoint value
(cooling)
8.5 PC21 PC22 °C UT
SSC1 Sets the summer outlet setpoint offset value 0.0 -20.0 20.0 °C UT
SPH1 Sets the winter outlet setpoint value (heating) 44.0 PC23 PC24 °C UT
SSH1 Sets the winter outlet setpoint offset value 0.0 -20.0 20.0 °C UT
MAINTENANCE TECHNICIAN - INSTALLER PARAMETERS
PSd2
Sets the Maintenance technician - Installer
level password
0 -999 9999 IS-V
PM91
Sets the last date maintenance was performed
on the system (year)
2007 2007 2060 MA-F
PM92
Sets the last date maintenance was performed
on the system (month)
1 1 12 MA-F
PM93
Sets the last date maintenance was performed
on the system (day)
1 1 31 MA-F
CALIBRATION
PM81
Calibration of the heating water outlet
temperature probe
0.0 -20.0 20.0 °C MA-CA
COMPRESSORS
PC04
Minimum time for which the compressor must
remain on even if switch-off has been
requested
20 0 999 Sec IS-C
PC05
Minimum time for which the compressor must
remain off even if switch-on has been
requested
120 0 999 Sec IS-C
PC06
Minimum time that must pass between two
switch-ons of the same compressor.
360 0 999 Sec IS-C
PC07 Minimum time for switch-on of compressor 1 60 0 999 Sec IS-C
PC08
Minimum time for switch-on of compressor 2
(winter mode)
10 0 20 Min IS-C
PC09
Minimum time for switch-on of compressor 2
(summer mode)
60 0 999 Sec IS-C
PC10
Compressor 1 block delay due to high
temperature
240 0 999 Sec IS-C
OUTLET SET LIMITS
PC21 Outlet summer setpoint minimum value 5.0 -15.0 SPC1 °C IS-R
PC22 Outlet summer setpoint maximum value 20.0 SPC1 23.0 °C IS-R
PC23 Outlet winter setpoint minimum value 30.0 23.0 SPH1 °C IS-R
PC24 Maximum value of the winter setpoint 44.0 SPH1 70.0 °C IS-R
PUMPS and FLOW SWITCHES
PP04
Minimum time that must pass between the
switch-on of the pumps and switch-on of the
first compressor
60 1 999 Sec IS-P
PP05 Minimum time that must pass between switch- 60 1 999 Sec IS-P